SYSTEM DESIGN INFORMATION
27
These detectors are designed and manufactured to protect against other hazards as defined in
paragraph 1.2.7 of Annex I1 of the ATEX directive 94/9/EC.
The one special condition of the certification is that, when using the fitted cable from the FV312
series detectors, this cable must be suitably terminated and protected from impact. See the
installation section for installation recommendations.
The detectors are also designed to comply with the requirements of Factory Mutual FMRC 3600
and FMRC 3615 for use in hazardous area locations Class I, Div 1, Group B, C, D and Class II
Group E, F G and Class III. The certified label for the FV300 detectors are shown in Fig. 21.
4.9.2 OTHER APPROVALS
The FV300 FlameVision detectors have been designed to and comply with requirements of Factory
Mutual FMRC 3260, the approval standard for Radiant Energy-Sensing Fire Detectors for
Automatic Fire Alarm Signalling.
4.10 MARKING
All the marking required by the various approval bodies is on the front plate (see Fig. 21) with the
exception of the Year of Manufacture/Construction which is stated on a label affixed to the rear of
the front case assembly. This is only visible when the front case assembly is unbolted from the
base assembly.