COMMISSIONING
44
Notes:
1) (*) When switch 1-1 is turned off (default) then DIP switches 2 to 8 are ignored
and all detector settings must be made using the PC configuration tool. If switch
1-1 is on, then the primary options are set by the DIP switches and can be
supplemented by advanced options set using the PC configuration tool.
2) For detectors with V1.001 software, when the DIP switches are active the action
of switch 5, Alarm Latching, is inverted (Off = Alarm Latching Disabled, On =
Alarm latching enabled).
3) The detector is supplied with the default configuration shown in Table 2.
7.2.3 4-20mA MODE SWITCH (SW2)
The 4-20mA output can operate in either a source or sink mode. This is selected on switch SW2,
see Fig. 28.
Switch Function
Action
Off (Default) On
1-1 Remote Configuration(*)
Ignore DIP switch settings
(Use programmed settings)
Use DIP switch settings
1-2
Alarm Delay Refer to Table 3 Delay Options
1-3
1-4 Reserved Set in Off position
1-5 Alarm Latching Latching Non-Latching
1-6 Fault Latching Non-Latching Latching
1-7 Window Heater Off On
1-8 OPM Man/Auto Automatic Manual
Table. 2 Configuration DIP Switches
SW
1-2
SW
1-3
Delay
Description
Alarm / Prealarm
ON condition
Alarm / Prealarm
OFF condition
Off On SHORT
1.5 seconds over threshold
in any 4 second period
10 seconds under
threshold
Off Off MEDIUM (Default)
4.5 seconds over threshold
in any 8 second period
10 seconds under
threshold
On Off LONG
9 seconds over threshold
in any 12 second period
12 seconds under
threshold
On On EXTRA LONG
12 seconds over threshold
in any 15 second period
15 seconds under
threshold
Table. 3 Delay Options