Breakaway tab
4. Device Enrollment
The 7-digit serial number located on the back of the smoke detector housing must be enrolled
on the alarm systems control panel. See the Receiver Installation Manual and follow the enroll-
ment procedure. For placement tests remove the detector from its backplate for one second
(tamper) and then reattach. Wait at least 30 seconds for the test result before activating again.
A general description of the procedure is provided in the following flow chart:
Step
Procedure
1
See the Installation Manual for the alarm system that the device is being enrolled on, to
ensure that the proper steps are used.
2
Enter the Device Enrollment option through the specified method and select the
appropriate option to add the new device.
3
Enroll the device by inserting the batteries to power up the device and enter the Device
ID. For example, ID No. 202-XXXX.
NOTE: When enrolling the SMD-429 detector to PowerMaster panels with version 19.4
or lower, the detector will be enrolled as a Smoke and Heat detector ID 201-
xxxx, and labeled Smoke and Heat in the panel.
4
Select the desired Zone Number.
5
Configure any device parameters that are required. Enter the DEV SETTINGS menu
and select the required options to configure the detector:
Option Configuration Instructions
Burglary Siren Select to enable a burglary alarm.
Options: ON or OFF (default)
Fire Siren Select to enable a fire alarm.
Options: ON or OFF (default)
Gas / CO Siren Select to enable a gas alarm.
Options: ON or OFF (default)
Flood Siren Select to enable a flood alarm.
Fire Siren Options: ON or OFF (default
6
Mount and test the detector. See Smoke Detector Unit Test for information on testing the
device. In addition, see the alarm systems Installation Manual that the device is enrolled
on for other test procedures that are required.
5. Test Unit
NOTE: The central monitoring station if used, should be notified prior to the test being gen-
erated. This prevents a false alarm and an unnecessary response from the central mon-
itoring station.
Initiate test by pressing the test button for 5 seconds minimum. Alarm activation is indicated by
the flashing red LED, the sounder, and transmission of the alarm signal to the control panel.
The detector restores to normal when the test button is released.
NOTE: Allow a minimum of 20 seconds after power up and after test, alarm or tamper restore
activations.
NOTE: If the detector is in one of the following states when a test is initiated; it will not enter an
alarm state:
l Compensation Trouble
l Other internal faults that could prevent a smoke or heat alarm
Owner's Instructions
Fire Safety In The Home
Most fires occur in the home, and to minimize this danger, it is recommended that a household
fire safety audit be conducted and a family escape plan be developed.