Blast Chiller Touch Screen Manual
65
Rev08/04/2015
Parameter Description 5 PANS 115V 5 PANS 230V
SELF CONTAINED 230V
TROLLEY
LBT minumum evaporator temperature related to set point [°C/°F] 50 50
50 50
EDT choking evaporator fan temperature range [°C/°F] 59 59
59 59
FEN minimum evaporator fan speed % [num] 25
25 25 25
FEX maximum evaporator fan speed % [num] 95
95 95 95
DOO max open door time before door alarm [sec] 60
60 60 60
FCE condenser fan set point [°C/°F] 77 77
77 77
HYF upper differential condenser fan action [°C/°F] 9 9
9 9
MCT max condenser temperature [°C/°F] 131 131
131 131
DCN dirty condenser threshold [°C/°F] 0 0
0 0
GAS low refrigerant amount alert threshold [°C/°F] 0 0
0 0
DCR
differential for restarting blast chiller after high condenser temperature
[°C/°F]
18 18
18 18
RMT stop time during high condenser temperature [sec] 180
180 180 180
PMT max high condenser event before high temp. Alarm [num] 3
3 3 3
TPB time threshold for high condenser temp. Alarm [min] 30
30 30 30
DTE defrost ending temp related to evap. Probe [°C/°F] 41 41
41 41
DRP dripping time after defrost [sec] 60
60 60 60
DTO defrost timeout [min] 10
10 10 10
ITD interval between two consecutive defrosts [hours] 8
8 8 8
DCD max on-time drain heater [min] 8
8 8 8
SDT ice detecting sensitivity in smart defrost mode [num] 0
0 0 0
SD1 first daily defrost [hour] 0
0 0 0
SD2 second daily defrost [hour] 0
0 0 0
SD3 third daily defrost [hour] 0
0 0 0
SD4 fourth daily defrost [hour] 0
0 0 0
SPX door frame heater set point [°C/°F] 14 14
14 14
COS average power factor of equipment [num] 5
5 5 5
PR1 declared power connected to relay1 [num] 0
0 0 0