16
GB/IE/NI/CY/MT
Code for rotary switch
41
RS485 functionEV charger No.
0OFFEV charger 1
1MASTEREV charger 2
2SLAVE 1 EV charger 3
3SLAVE 2EV charger 4
4SLAVE 3EV charger 5
5SLAVE 4EV charger 6
6SLAVE 5EV charger 7
7SLAVE 6EV charger 8
8SLAVE 7EV charger 9
9SLAVE 8EV charger 10
The setting 0 is the factory setting. It is used when only one EV charger is going to be connected.
Setting the Smart Meter Gateway:
 This address is made up as follows: Address = Addr1 x10 + Addr2
Addr1x10Addr2 x1Address
000
011
.........
099
1010
1111
.........
9999
Software Update:
 A software update may only be performed by a trained professional. It is carried out using the USB
port
43
and the Update button
37
.
Modbus communication:
Modbus communication takes place using the RS485 interface.
The following registry table is implemented: