Set language
TIME Set current time:
1. Minute 2. Hour
GERMAN
PARAMETERS DISPAYED AT THE COMMISSIONING STAGE
Default IVValue rangeDesignation
INSTALLATION
YEAR
Set current date
MONTH
Set current date
DAY
Set current date
BUS ID
11
11
1
Enter heating circuit number “1”:
00-15 Standard 01
BUS ID
22
22
2
Enter heating circuit number “2”:
00-15 Standard 02
5K SENSOR
00 = 5 KOhm NTC sensor
01 = 1 kOhm PTCsensor, code no. required;
after input, there is a restart of the controller
RETURN
end of INSTALLATION
Start INSTALLATION, Set value, Save value and next value
Start INSTALLATION, Set value, Save value and next value
Acc. to versionGERMAN GERMAN
(-20) (20)CONTRAST 0
Sensor, weekdayDISPLAY SEL - - - -
Exit level usingRETURN
Default IVValue rangeDesignation
HOT WATER
00, 01 (OFF / ON)1X DHW 00 = OFF
10 °C - 70 °CDHW-TEMP 1 60 °C
10 °C - 70 °CDHW-TEMP 2 60 °C
Exit level usingRETURN
10 °C - 70 °CDHW-TEMP 3 60 °C
OK - 70KBOB-VALUE 0K
00, 01 (OFF / ON)CIRCL-P-DHW 00 = OFF
00, 01 (OFF / ON)ANTILEGION 00 = OFF
PARAMETERS PROGRAMMABLE BY THE USER