36
4 15 BLOCK
No gas or failed burner ignition.
Check the gas supply or that
the ignition/detection electrode
is working properly (4).
11 16 PARASITE FLAME
Flame detected upon ignition.
Check the wiring of the Ign/Det.
electrode and remove any ox-
idation, check for humidity be-
tween drain wire and ceramic,
if necessary, press the unblock
key, if the anomaly persists,
replace the electrode (4).
17 PARASITE FLAME
Flame detected after swtich-off.
Check the wiring and for any
leaks from the gas valve (3)
(3) if needed replace the gas
valve.
46
CHIMNEY
18 FLUE GAS COLLECTOR
Intervention of the ue gas col-
lector safety thermostat (23).
Check the body’s internal heat
exchanger, in case of ano-
malies, DO NOT RESET the
boiler.
It is possible manually reset
the thermostat and press the
unlock button on the panel,
only in case there was a pro-
blem (solved) of connection
wiring.
19 22 FLAME CONTROL
Flame control damaged
Replace the board.
INCONVENIENCES SOLUTIONS
Flame noisy
in cold ignition
Act on parameter ‘’IG’’ using the REGOLAFACILE section ‘’TECHNICAL
MENU’’ TSP parameters increasing the value by 5 ÷ 10 % max
Flame noisy in
steady-state conditions
increase the CO
2
value
- max value for methane gas = 9.6 %
(min value > 9.1 %)
- max value for propane = 11.0 %
(min value > 10.3 %)
Flame noisy in
modulation
At the end of its life cycle the product must not be disposed of as urban waste. It can be taken to
a special recycling centre managed by the local authorities, or to a dealer who offers this service.
Separate disposal of a domestic appliance avoids possible negative consequences for the
environment and human health deriving from inappropriate waste handling and allows the recovery
of the materials of which it is made, in order to obtain signicant energy and resource savings.