The Dt between supply and return boiler must
never be less than 15 ° K.
NOTE:
The use of a mixing header tted between the
boiler circuit and the system circuit is always ad-
visable. It becomes INDISPENSABLE if the sy-
stem requires ow rates superior to the
maximum permitted boiler ow rates, which is to
say lower than 15K.
Avaible Head m.c.a. (m/H
2
O)
The table provides an indication the flow the pump in function of the Dt of the primary circuit.
KONf 100 KONf 115
Power supply in kW kW 99,5 115
Max ow rate demanded l/h (Dt 15 K) l/h 5700 6600
Nominal ow rate request (Dt 20 K) l/h 4280 4950
Power supply in condensation (50/30) kW 105 120,3
Max ow rate demanded l/h (Dt 15 K) l/h 6020 6897
Nominal ow rate request (Dt 20 K) l/h 4520 5173
2.4 - DIAGRAM OF FLOW RATE/PRESSURE AVAILABLE FOR INSTALLATION
Q = Flow rate (l/h)