Installation Instructions
Preliminary operations:
Fit the Ø 100 mm smoke outlet hose
provided in the package as shown.
3.6 - FLUE GAS EXHAUST PIPE CONNECTION (Forced draw boiler)
B23P
TOTAL LENGTH ( LS exhaust)
SINGLE Ø100
FROM [m] TO [m]
1 42
Connection to a combustion products evacuation
pipe outside the room; the combustion air is tak-
en directly from the room where the appliance is
installed.
C63x C63
Boiler intended for connection to a combustion air
intake and combustion products evacuation system,
approved and sold separately
ATTENTION:
The ue must comply with standards
in force.
To connect the ue gas exhaust pipe, local and na-
tional standards must be observed
In the event the boiler is replaced, ALWAYS re-
place the ue gas pipe as well.
The boiler is type approved for the exhaust congu-
rations listed below:
ATTENTION:
For the type of connection B23P the
room follows the same installation rules
for boilers with natural draught.
Please note:
These values relate to exhausts/
made by means of rigid pipes and
smooth original UNICAL.
CAUTION
LT total length is a reference value
for the dimensioning of the ducts of A
(intake) and S (Exhaust). Subtracting
the values of LT reported, at values of
bends* / terminals* / extensions* you
get the value:
if > 0 = OK - POSSIBLE conguration
if < 0 = NO - WRONG conguration
(*) Values in the MT018 available on the website.