2.5.1 - TECHNICAL DATA ACCORDING ErP DIRECTIVE
KONf 100 KONf 115
Element Symbol Unit
Eective nominal output Pnominale kW 99 112
Seasonal energy eciency to heat
the room
ƞ
s % 94 92
Season eciency class to
discharge
A A
For boilers to heat the room
and mixed boilers: useful heat output
Useful heat output with
high temperature capacity
(Tr 60 °C / Tm 80 °C)
P
4 kW 98,8 111,5
Rated heat output eciency
with high temperature capacity
(Tr 60 °C / Tm 80 °C)
ƞ
4 % 89,0 87,4
Useful power at 30% of the rated heat
output with low temperature
capacity (Tr 30 °C)
P
1 kW 32,2 36,9
Performance at 30% of the rated heat
output with low temperature
capacity (Tr 30 °C)
ƞ
1 % 98,5 96,5
Boiler with output range adjustment: YES / NO NO NO
Auxiliary electricity consumption
With a full load elmax kW 0,289 0,314
With a partial load elmin kW 0,156 0,160
Standby mode P
SB kW 0,018 0,028
Other elements
Heat dispersion on standby P
stb kW 0,641 0,642
Nitrogen oxides emissions NOx
Mg/kWh
43 46
For mixed heating appliances
Declared load prole - -
Water heating energy eciency ƞ
wh % - -
Daily consumption of electricity Qelec kWh - -
Daily consumption of fuel Qfuel kWh - -
Internal sound power level Lwa dB (A) - -
Seasonal DHW eciency class
- -