26
KONf 100
Type of
Gas
Supply
Press.
Ø
Nozzles
Collector
diaphragm
Fan speed CO
2
levels Start-up
power.
[mbar] (mm) [Ø/mm] min max [%] [%]
FL [%FU] FH
[% FU]
min max IG
Gas nat. (G20) 20 - 14 25 85 8,6 9,3 28
Gas nat. (G25) 25 - - 22 84 8,6 9,1 28
Propano (G31) 37 - 14 23 78 9,6 10,6 28
KONf 115
Type of
Gas
Supply
Press.
Ø
Nozzles
Collector
diaphragm
Fan speed CO
2
levels Start-up
power.
[mbar] (mm) [Ø/mm] min max [%] [%]
FL [%FU] FH
[% FU]
min max IG
Gas nat. (G20) 20 - 14 25 97 8,6 9,3 28
Gas nat. (G25) 25 - - 22 92 8,6 9,1 28
Propano (G31) 37 - 14 23 92 9,6 10,6 28
If the CO2 percentage is too low, check if the air
and smoke ducts are not obstructed.
Check the levels of CO2 often, especially with low ow rates. They refer to the boiler with a closed combustion chamber.
NOZZLES - PRESSURE - FLOW RATES TABLE
3) Conclusion of the basic calibrations
- once the CO
2
values at minimum and maximum output
have been checked and any adjustments have been made
(sections 1-2):
- disable the timed “calibration” function by switching o the
main switch.
For proper operation, the CO
2
values must be
calibrated with particular attention, observing
the values indicated in the table.
- close the ue gas inspection sample points of the intake and
exhaust terminal
- check that there are no gas leaks.
If they are not obstructed, check if the burner and/or the
exchanger (aluminium sections) are well cleaned.