KONf 100
Type of
Gas
Supply
Press.
Ø
Nozzles
Collector
diaphragm
Fan speed CO
2
levels Start-up
power.
[mbar] (mm) [Ø/mm] min max [%] [%]
FL [%FU] FH
[% FU]
min max IG
Gas nat. (G20) 20 - 14 25 85 8,6 9,3 28
Gas nat. (G25) 25 - - 22 84 8,6 9,1 28
Propano (G31) 37 - 14 23 78 9,6 10,6 28
KONf 115
Type of
Gas
Supply
Press.
Ø
Nozzles
Collector
diaphragm
Fan speed CO
2
levels Start-up
power.
[mbar] (mm) [Ø/mm] min max [%] [%]
FL [%FU] FH
[% FU]
min max IG
Gas nat. (G20) 20 - 14 25 97 8,6 9,3 28
Gas nat. (G25) 25 - - 22 92 8,6 9,1 28
Propano (G31) 37 - 14 23 92 9,6 10,6 28
If the CO2 percentage is too low, check if the air
and smoke ducts are not obstructed.
Check the levels of CO2 often, especially with low ow rates. They refer to the boiler with a closed combustion chamber.
NOZZLES - PRESSURE - FLOW RATES TABLE
3) Conclusion of the basic calibrations
- once the CO
2
values at minimum and maximum output
have been checked and any adjustments have been made
(sections 1-2):
- disable the timed “calibration” function by switching o󰀨 the
main switch.
For proper operation, the CO
2
values must be
calibrated with particular attention, observing
the values indicated in the table.
- close the ue gas inspection sample points of the intake and
exhaust terminal
- check that there are no gas leaks.
If they are not obstructed, check if the burner and/or the
exchanger (aluminium sections) are well cleaned.