Page 8 of 27 July 2005 UM-6800A Rev1.3
CPU Function
Monitoring external inputs from vital input boards and non-vital input
boards
Processing vital external inputs and executing logic defined in the
application software
Driving vital output boards as required by the application program
Monitoring and controlling serial communication ports (links to other
controllers)
Testing individual vital input and output channels for faults (in parallel
with control of these channels) and responding to detected faults
Monitoring system internal operation for faults and responding to detected
faults
Controlling power to vital outputs through the card file power supply and
an external VCOR (fail-safe function)
Recording system faults and routine events in user-accessible memory
Fig. 2 Ref Label Device Purpose
1, 2 (None)
4-character alpha-
numeric displays
On-site configuration programming menus
and options.
3
A, B, C, D, E
Yellow LEDs Reserved for serial link status.
4
1, 2, 3, 4, 5, 6, 7, 8
Red LEDs User-defined in application software.
5
ON LINE
Green LED
When lit, indicates normal system operation
(successful diagnostics).
6
VPP ON
Yellow LED
When lit, indicates FLASH +5V or +12V
programming voltage enabled (via board
jumper).
7
RESET
Green LED
When lit, indicates that the system is in reset
mode.
8
RESET
Momentary pushbutton
When pressed, resets the CPU. Also used to
place the CPU in the reset mode.
9
MENU L-R
3-position (return-to-
center) toggle switch
Used to search main program menu items
shown on displays.
10
MENU UP-DOWN
3-position (return-to-
center) toggle switch
Used to select main program menu items
shown on displays.
11
ADJUST UP-DOWN
3-position (return-to-
center) toggle switch
Used to cycle through configuration values to
be selected with “ACTION” switch.
12
ACTION ACCEPT-
REJECT
3-position (return-to-
center) toggle switch
Executes or cancels configuration value
selected with
“ADJUST”
switch.
13
RS-232 DTE
Diagnostic Link
Connector
DB9, RS-232 Connector
(DTE)
Used for connection to Maintenance PC for
System monitoring diagnosis.