C4.2 FAULT RELAY OPERATION. When the J3 jumper is in the
FAULT position, the relay will close when any fault shown in C5 occurs.
C5. FAULT RESET MODE:
The SOLUTIONi control can respond to three types of faults:
1. WELDING CURRENT out of customer-set window
2. ELECTRODE FORCE out of customer-set variation window
3. LINE VOLTAGE out of +/-10% variation from baseline
Faults in any of these three categories can close a FAULT relay for a selectable
time and can also stop the welding sequence if so desired. You can also set the
SOLUTIONi control to close on a successful weld.
The faults will also be shown on the display.
To set the desired FAULT RESET MODE, Press:
The display will show:
Push and the display will show:
PROGRAM
9
8
2
FAULT RESET MODE IS:
KEYPAD & INITIATE =1
Want to change? Push
the YES or NO button
YES
FAULT RESET MODE IS:
KEYPAD & INITIATE =1
KEYPAD & KEYLOCK =2
AUTOMATIC =3
STEP
ENTER