Universal Chilling Systems, LLC.
Manual Model 10 Air Cooled Chiller
5. Settings
Default password of repairman's: 1 2 3, that is the key: START, INQUIRE, SET.
When system is in STOP page in the user's main face, press and <+> at the same time, it will
enter SYS. SETTINGS page as below.
Then input the password, press OK. If is the wrong password, the show will be below:
Press RETURN to come back to main face.
The password is two levels, after password of manufacturer’s or repairman’s is put in, it will enter RUN
SETTINGS menu as below:
1: RUN SETTINGS
2: MODIFY PWD
When enter by the repairman's password, there will be 2 items in front of the menu.
1: RUN SETIINGS
2: MODIFY PWD.
I.
RUN SETTINGS
In RUN SETTINGS, select RUN SETTINGS by and , press OK to enter RUN SETTINGS show
below:
1: SYS. SETTINGS
2: SETTINGS 1
There are 10 items for RUN SETIINGS, and there are sub-items under each item. The 10 items are
below:
1.
SYS. SETTINGS (Manufacturer's password can set all; repairman's password can change only
the items of POINT and SWITCH)
2.
TIME SETTINGS 1
3.
TIME SETTINGS 2