14 vacon Receipt of delivery
Telephone: +358-201-2121 Fax: +358-201-212 205
3
Figure 3-2. Vacon NXL type designation code for sizes MF4 - MF6.
3.2 Storage
If the frequency converter is to be kept in store before use make sure that the ambient conditions
are acceptable:
Storing temperature 40…+70
°C
Relative humidity <95%, no condensation
3.3 Maintenance
In normal conditions, Vacon NXL frequency converters are maintenance-free. However, we
recommend to clean the heatsink (using e.g. a small brush) whenever necessary.
Most Vacon NXL drives are equipped with a cooling fan, which can easily be changed if necessary.
NXL 0004
C 2 T 1 SSS 00 AA
5
Product range: NXL = NX Light
Nominal current (low overload)
Maximum continuous current of the unit at 40 deg
e.g. 0007 = 7 Amps.
Nominal mains voltage:
2 = 208–240Vac, 5 = 380–500Vac
Control keypad:
B = No control keypad
C = standard seven-segment keypad
EMC emission level:
Hardware modifications; Supply - Mounting - Boards
SSS = Standard
SSV = Varnished PCB’s
Enclosure classification:
2= IP21
5= IP54
Brake chopper
1 = internal brake chopper
Slot E: Factory installed I/0 boa
rds,fieldbus boards and expanders:
00= no board, AA = OPT-AA expander I/O board,
AI = OPT-AI expander I/O board, e.g. C3=Profibus board
Slot D: Factory installed fieldbus boards:
00= no board, e.g: CI = Modbus/TCP Board,
C3 = Profibus board
C = Fulfils EN 61800-3:2004+A1:2012, category C1
H = Fulfils EN 61800-3:2004+A1:2012, category C2
T = Fulfils the standard EN 61800-3:2004+A1:2012 when used in IT
networks
11554_uk