ELECTRICAL CONNECTION vacon • 21
24-hour support: +358 (0)201 212 575 • Email: vacon@vacon.com
Model
Cross section
NXV0010 10mm
2
NXV0015 10mm
2
NXV0020 16mm
2
NXV0025 16mm
2
NXV0030 16mm
2
NXV0040 25mm
2
NXV0050 25mm
2
NXV0080 35mm
2
NXV0100 35mm
2
Table 5-5 Panel earthing cable dimensions
The minimum cable cross section is calculated in compliance with loading capacity of cables. The
recommended cross section is calculated in compliance with 1-% voltage drop for a cable 100 m in
length.