The S- type dU/dt filters are forced air cooled and require a 220 V AC power supply for their fans.
The filter has a build-in thermal switch, which indicates if the filter temperature has exceeded the
safe limits. This NC contact can be wired to the External fault input of the drive - see the wiring
schematic in Figure 10.
Check the input parameterization from the relevant drive application manual. If the external fault
input is used for other purposes, you can also connect the fault contact in series with the RUN or
the RUN ENABLE command - for their terminal assignment see the relevant application manual.
Figure 10. Wiring schematic of the S-type dU/dt filter external fan supply and thermal supervision NC
connection