8
Α/Α
Abbreviation
Description of Parameters
FROM TO
1
SYSTEM
Select Application ( See pages 3 & 4) .
1 4 1
2
HST
Higher Sink Temperature
Maximum desired temperature heat sink .
20°C 95°C 80°C
3
DTS
Differential Temperature Sensors
Differential temperature S1-S2 ( for all applications ) and
the S3-S2 ( only for application 4 ) which will trigger the
R1 ( for all applications ) and the R2 ( only for application
4 ) respectively.
ODT 30°C 8°C
4
ODT
Off Difference Temperature
Differential temperature S1-S2 ( for all applications ) and
the S3-S2 ( embodiment 4 only ) which will turn off the R1
( for all applications ) and the R2 ( only for application 4 )
respectively.
1°C DTS 3°C
5
CPD
Clock Pump Delay
Delay activate circulators collectors.
0 sec 240 sec 30 sec
6
MCT
Minimum Collector Temperature
Low temperature collectors for which actuated pumps col-
lectors.
10°C 80°C 10°C
7
MTC
Maximum Temperature Collector
Overheat protection panels.
100°C 150°C 110°C
8
FPC
Frost Protection for Collector
Frost protection panels.
-10°C 5°C 3°C
9
MST
Minimum Sink Temperature
Minimum temperature in the DHW storage tank (only ap-
plications 2 and 3 ) .
20°C 80°C 35°C
10
DAS
Differential Auxiliary source
Different minimum temperature in DHW storage tank
(only applications 2 and 3 )
10°C 3°C 5°C
11
EXIT
Exit from Menu
Setup Menu: TABLE 1
default