Appendix
0020285064_00 aroSTOR Operating instructions 17
Fault Cause Solution
The condensate does not
drain off (water under-
neath the product).
The condensate discharge hose is
partly or completely blocked
Check the condensate
discharge hose.
There is a kink in the condensate
discharge hose and this is forming a
trough.
The condensate discharge hose is not
installed.
Consult your competent
person.
The electric back-up
heater is not working.
The ESC contact or a programmed
operating time is preventing operation
(ECO symbol is lit up).
Check the time program-
ming and consult your
competent person.
The safety cut-out for the electric back-
up heater has been tripped as a result
of overheating (> 87 °C).
Consult your competent
person.
Other faults Consult your competent
person.
B Optimising energy consumption
B.1 Using a low tariff and a control cable connection
Settings made by the end user
Setting/function Particularly econom-
ical
Average For increased com-
fort
Target temperature 45 °C 55 °C 65 °C
Time programming None None None
Holiday mode For absences of
more than 24 hours
For absences of
more than 3 days
For absences of
over a week
Boost mode Never Occasionally Often
Settings made by the competent person
Setting/function Particularly econom-
ical
Average Particularly expens-
ive
Anti-legionella cycle No 7 (weekly) 1 (daily not re-
quired)
Minimum temperature No 43 °C 43 °C
MAX. TIME function No Auto 4 hours
Load relief level for high-
tariff periods (HT)
0 (Operation of the
immersion heater
and the heat pump
prevented during
high-tariff periods)
1 (Operation of the
immersion heater
prevented during
high-tariff periods)
2 (Deactivation of
the load relief cir-
cuit)
*) Exception: The air temperature lies outside the range between -7 °C and +35 °C. In this case,
operation of the back-up heater is permitted.

Table of Contents

Other manuals for Vaillant aroSTOR VWL B 200/5 UK

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant aroSTOR VWL B 200/5 UK and is the answer not in the manual?

Vaillant aroSTOR VWL B 200/5 UK Specifications

General IconGeneral
TypeHeat Pump Water Heater
Capacity200 liters
Energy Efficiency ClassA+
Power Supply230V / 50Hz
ErP classA+
RefrigerantR134a
Insulation thickness50 mm
Diameter600 mm
Max Water Temperature65 °C
COP (Coefficient of Performance)3.3 (A15/W10-55 according to EN 16147)