viewLinc 4.0 Administrator Guide 139
Q: My network uses a combination of Vaisala Veriteq devices and
300 Series Transmitters. How can I add them quickly?
A: To add multiple transmitters or a combination of devices
and transmitters at one time, create a .txt definitions file with
one device or transmitter defined per line. Add fields to
identify the device class and device properties (separating
each field with a tab).
To set vcom type devices (Vaisala Veriteq devices), define
the com port number to which your device is connected. For
example:
vcom com_port=101
vcom com_port=102
vcom com_port=103
To set hmt330 type devices (300 Series Transmitters), define
the following:
sample_rate = the internal sample rate of the device
timeout = the timeout for communication events
connection = the type of connection, comport or tcp
com_port = a com port number to which your device is
connected (values for comport connections are user-
defined)
ip_address = the IP device address of your devices (tcp
connection)
ip_port = the tcp port (values for tcp connections,
ip_address and ip_port, are user-defined)
Common values for both tcp and comport connections:
sample_rate = 10s, 90s (default), 12m, 2h, 12h, 2d,
or 12d
Optional values for comport connection:
baud = 300, 2400, 4800, 9600, 19200 (default), 57600,
or 115200
•stopbits = 1(default) or 2
databits = 7 or 8(default)
parity = odd, even or none(default)