Page #35 background imageLoading...
Page #35 background image
Valent Controls IOM 35 IOM-C1-0616
Part Number 474626
Description =Editable**
Object Name
Object Type
Instance
Energy Recovery Control Output
Energy Recovery
Analog Value
48
Space Unoccupied Cooling Setpoint
Space Unoccupied Cooling
Setpoint
Analog Value
49
Space Unoccupied Heating Setpoint
Space Unoccupied Heating
Setpoint
Analog Value
50
Space Unoccupied Humidity Setpoint
Space Unoccupied Humidity
Setpoint
Analog Value
51
Space Temperature Heating Setpoint
SpaceHeatingSetpoint
Analog Value
52
Space Temperature Cooling Setpoint
SpaceCoolingSetpoint
Analog Value
53
Space Temperature Setpoint Offset
SpaceTempSptOffset
Analog Value
54
Air Flow Monitoring Exhaust Cone Flow
Exhaust CFM
Analog Value
55
Outside Air Damper Minimum Position
OAD Min Pos
Analog Value
56
Active Space Temperature Setpoint
Active Space Temperature Setpoint
Analog Value
57
Space Setpoint Slider
Space Setpoint Slider
Analog Value
58
System Start Command
SystemStart
Binary Value
1
Shutdown Input Status
RunStopStatus
Binary Value
2
Supply Fan Status
SupplyFanStatus
Binary Value
3
Exhaust Fan Status
ExFanStatus
Binary Value
4
Heat Wheel Status
HeatWheelStatus
Binary Value
5
Compressor 1 Status
Compr1Status
Binary Value
6
Compressor 2 Status
Compr2Status
Binary Value
7
Compressor 3 Status
Compr3Status
Binary Value
8
Compressor 4 Status
Compr4Status
Binary Value
9
Gas Heat Enable, Stage 1
GasHeatEnaStg1
Binary Value
10
Gas Heat Enable, Stage 2
GasHeatEnaStg2
Binary Value
11
Gas Heat Enable, Stage 3
GasHeatEnaStg3
Binary Value
12
Head Pressure Digital Output Status
HeadPressureDO
Binary Value
13
Reversing Valve Position
RevValve
Binary Value
14
Enables BAS to Control Occupancy *
BAS_Occ_Enable
Binary Value
15
BAS Occupancy Command *
BAS_Occ_Command
Binary Value
16
BAS Cooling Disable Request *
Cooling Disable Request
Binary Value
17
BAS Heating Disable Request *
Heating Disable Request
Binary Value
18
BAS System Emergency Shutdown Command *
System Shutdown BAS
Binary Value
19
Alarm Reset
AlarmReset
Binary Value
20
System Alarm Status
Alarm Status
Binary Value
21
Shutdown Input Alarm
Shutdown Input Alarm
Binary Value
22
Supply Fan Alarm
Supply Fan Alarm
Binary Value
23
Exhaust Fan Alarm
ExhaustFanAlarm
Binary Value
24
Damper End Switch Alarm
EndSwitchAlarm
Binary Value
25
Circuit A High Low Pressure Alarm
HPC_LPC_A_Alarm
Binary Value
26
Circuit B High Low Pressure Alarm
HPC_LPC_B_Alarm
Binary Value
27
Refrigerant Pressure Transducer Circuit A Alarm
RefPressureAAlarm
Binary Value
28
Refrigerant Pressure Transducer Circuit B Alarm
RefPressureBAlarm
Binary Value
29
Supply Temperature Sensor Alarm
SupplyTempSensorAlarm
Binary Value
30
Exhaust Temperature Sensor Alarm
ExhaustTempSensorAlarm
Binary Value
32
Mixed Air Temperature Sensor Alarm
MixedTempSensorAlarm
Binary Value
33
Outdoor Air Relative Humidity Sensor Alarm
OA_RH_Sensor_Alarm
Binary Value
34
Outdoor Air Temperature Sensor Alarm
OASensorAlarm
Binary Value
35