Valent Controls IOM 53 IOM-C1-0616
Part Number 474626
Compressor 4
Turns Compressor 4 on or off.
Digital Scroll
Enter a value for the digital scroll compressor.
Modulating Heat
Enter the percentage of modulating heat to use
in override mode.
Electric Heat
Enter the percentage of electric heat to use in
override mode.
Heat 1
Turns stage 1 heating on or off.
Heat 2
Turns stage 2 heating on or off.
Heat 3
Turns stage 3 heating on or off.
Space Setpoint
Enter the space temperature that the system
should control to when in override mode.
Supply Setpoint
Enter the supply temperature that the system
should control to when in override mode.
Hot Gas Reheat
Auto: Controls to the demand called for by the
main control sequence.
Manual: Controls to the demand set by the
Reheat Override point.
Reheat Override
Enter a percentage of reheat to run in override
mode.
Flat Plate
Auto: Controls the flat plate bypass damper to
the position determined by the controller.
Manual: Controls to the value set by the Flat
Plate Override point.
Flat Plate Override
Enter a position to control the flat plate bypass
damper. This value is used if Flat Plate is set to
Manual.
Pre-Heater
Turns the preheater on or off.
Coil Safety
Disables the Coil Low Limit Safety function.
Head Pressure
Auto: Controls the fan speed or water valve
position(s) to the values set by the controller.
Override: Controls the fan speed or water valve
position(s) to the values set by the following Fan
VFD/Valve A and Valve B points. This can be
set to Override only when the compressors are
off.
Fan VFD/Valve A
Enter the fan speed or position of water valve A,
depending on system configuration. These can
only be overridden if the compressors are off.
Valve B
Enter the position of water valve B. This can
only be overridden if the compressors are off.
Reversing Valve
Auto: Controls the heating or cooling mode
based on current unit conditions.
Manual: Controls the heating or cooling
components using the values for the following
valve override position.
Override: Enter a reversing valve position to use
in heating or cooling mode.