Timer Description Default
Time Sync Limit
TIME SYNC
LIMIT
Time limit within which time synchronization will not take place. Time synchronization
only takes place if system time and update time are outside this limit. (0300
seconds)
0sec.
Link Timeout
LINK TIMEOUT
Timeout for Ethernet link fault. (0–250 seconds; 0=Disabled) 0sec.
Camera Offline
CAMERA
OFFLINE
Time for camera to go offline. (10–9999 seconds) 10sec.
Frequent
FREQUENT
This attribute only applies to remote services. The number of hours within which a
zone must open if the zone is programmed with the Frequent attribute. (19999
hours)
336h (2
weeks)
Duress silent Time when duress will remain silent and not restorable from keypad. (0–999 minutes) 0min.
Holdup/panic
silent
Number of minutes that a holdup/panic will remain silent and cannot be restored from
the keypad. (0999 minutes)
0min.
Default times are dependent upon the Engineer configuration. The default times denoted may or may
not be allowable and is dependent on the configuration by the engineer.
Valid settings/ranges may be dependent on the security grade specified under Configuration >
System > Standards.
16.4 Areas
1. Scroll to AREAS and press SELECT.
2. Scroll to the desired programming option:
ADD For Domestic and Commercial Mode, the area type defaults to Standard.
In Financial Mode, select area type STANDARD, ATM, VAULT or ADVANCED.
Enter the name of the area and the preferred entry/exit time.
SPC4xxx/5xxx/6xxx Installation & Configuration Manual Engineer programming via the keypad
© Vanderbilt 2018 121 A6V10276959-d
11.2018