TCY3-T1102 Engineering Manual
Doc: 70-000003 V1.0, 20150710 © Vector Controls GmbH, Switzerland Page 17
Subject to alteration
Temperature input configuration
Parameter
Description
Range
Default
IP 00
TI1: External sensor / control input for loop 1
0 = not used, internal sensor is input for lp1
1 = external sensor is input for lp1
2 = auto change over
0…2
0
IP 01
TI1: Samples taken for averaging control signal
1…255
10
IP 02
TI1: Calibration
-10…10
0
IP 03
Alarm 1:
OFF = not active
ON = active
OFF, ON
OFF
IP 04
Alarm 1 low limit
-40…215 °C
5 °C (40 °F)
IP 05
Alarm 1 Hysteresis
0…100 °C
5 °C (10 °F)
IP 06
Alarm 2:
OFF = not active
ON = active
OFF, ON
OFF
IP 07
Alarm 2 high limit
-40…215 °C
50 °C
(122 °F)
IP 08
Alarm 2 hysteresis
0…100 °C
5 °C (10 °F)
Analog input configuration
Parameter
Description
Range
Default
IP 09
AI1: Calibration
-10…10
0
IP 10
AI1: Minimum limitation of input signal
0 Max %
0 %
IP 11
AI1: Maximum limitation of input signal
Min 100%
100%
IP 12
AI1: Lower display transformation value
-50…Max
0
IP 13
AI1: Upper display transformation value
Min…205
100
IP 14
AI1: Samples taken for averaging control signal
1…255
3
IP 15
AI1: Unit & range of analog input:
0 = no unit
1 = %
2 = °C / °F
3 = x10
4 = x100
0 4
1
Alarms 3 and 4 follow control input of loop 2
Parameter
Description
Range
Default
IP 16
Alarm 3:
OFF = not active
ON = active
OFF, ON
OFF
IP 17
Alarm 3 low limit
Acc. input
0%
IP 18
Alarm 3 hysteresis
Acc. input
5%
IP 19
Alarm 4:
OFF = not active
ON = active
OFF, ON
OFF
IP 20
Alarm 4 high limit
Acc. input
100%
IP 21
Alarm 4 hysteresis
Acc. input
5%