Press Function until the display shows:
To test individual tanks press Step, Change, Enter and Step. To test all tanks press Step twice
and the display will show:
To end the test manually press Change, Enter and Step; or to set a duration for the test press
Step. Select the test accuracy, either 0.20 gal/hr or 0.10 gal/hr. To change the setting press
Change and Enter. Press Step to continue. Enter the Test Duration in hours, press Enter and
Step. The display will show:
Press Enter to start the test. For individual tanks press Tank to go to the next tank.
START IN-TANK LEAK TEST
PRESS <STEP> TO CONTINUE
TEST CONTROL: ALL TANKS
TIMED DURATION
START LEAK TEST TANKS
PRESS <ENTER>
Do not start an in-tank leak test if there
has been a delivery to the tank to be
tested within the previous 8 hours. This
will result in an invalid test.
A delivery to a tank being tested results
in an invalid test.
Dispensing from a tank being tested wi
ll
cause a Sudden Loss Alarm.
To Start An In-Tank Leak Test