JT550 Series Inverter Manual
- 1 -
Preface
The JT550 is a high-performance and multipurpose industrial product aiming to
integrate synchronous motor drive with asynchronous motor drive, and torque
control, speed control with position control. It is designed with advanced vector
control technology and the latest digital processor dedicated for motor control, thus
enhancing product reliability and adaptability to the environment.
The JT550 adopts customized and industrialized design to realize excellent control
performance through optimized functions and flexible applications.
JT550 uses high power density design. Some power ranges carry built-in DC reactor
and brake unit to save installation space. Through overall EMC design, it can satisfy
the low noise and low electromagnetic interference requirements to cope with
challenging grid, temperature, humidity and dust conditions, thus greatly improving
product reliability.
This operation manual presents installation wiring, parameter setup, fault diagnosis
and trouble shooting, and precautions related to daily maintenance. Read through
this manual carefully before installation to ensure the AC Drive is installed and
operated in a proper manner to give full play to its excellent performance and
powerful functions.
It is the responsibility of the user or machine builder or installation contractor or
electrical designer/engineer to take all necessary precautions to ensure that the
system complies with current standards, and to provide any devices (including safety
components), required to ensure the overall safety of the equipment and personnel.
If there is any doubt with regards to the software version or the manual contents,
please contact us.

Table of Contents

Questions and Answers

  • M
    Maurice AdamsSep 18, 2025
    What to do when Veichi DC Drives reach the set total power-on time?
    • D
      Diana Adams DDSSep 18, 2025
      When Veichi DC Drives reach the set total power-on time, because the accumulated power-on time (F8.13) reaches the set value (F4.16), clear the records using the initiation of parameters.
  • C
    codykellerAug 25, 2025
    Why Veichi DC Drives show overcurrent at constant speed?
    • M
      Michael SmithAug 26, 2025
      If your Veichi DC Drives are showing overcurrent at a constant speed, the causes might be: a grounded or shorted inverter output circuit; vector control mode without parameter identification; low voltage; a sudden load added during operation; an undersized inverter model; or a shorted braking resistor. Here’s how to address it: eliminate the peripheral failure; initiate motor parameter identification; adjust the voltage to the normal range; choose rotational speed tracking start or start it after the motor stops; cancel the sudden load addition; use an inverter with a higher power level; and check the braking resistance.
  • D
    Donald Floyd DVMAug 27, 2025
    How to troubleshoot overvoltage during deceleration in Veichi DC Drives?
    • K
      Katherine LarsonAug 27, 2025
      To troubleshoot overvoltage during deceleration in Veichi DC Drives, consider these points. This issue may arise due to: high input voltage; an external force dragging the motor; short deceleration time; or missing braking units or resistors. Resolve the problem by: adjusting the voltage to the normal range; removing any external forces or adding braking resistors; increasing the deceleration time; and installing braking units and resistors.
  • T
    Tyler FinleyAug 27, 2025
    What causes overvoltage during acceleration in Veichi DC Drives?
    • C
      Charles WrightAug 27, 2025
      Overvoltage during acceleration in Veichi DC Drives can stem from several causes: the input voltage being too high, an external force dragging the motor during acceleration, the acceleration time being too short, or the absence of braking units or braking resistors. You can address this by: adjusting the voltage to the normal range; removing the external force or adding braking resistors; increasing the acceleration time; and adding braking units and braking resistors.
  • C
    Cynthia WattsSep 22, 2025
    What causes offload errors in Veichi DC Drives?
    • A
      Angelica ThompsonSep 22, 2025
      Offload errors in Veichi DC Drives occur when the operation current of the inverter is smaller than F9.64. To resolve this, confirm the removal of load or check if the parameter settings of F9.64 and F9.65 match the real situation.
  • R
    rodriguezhenryNov 22, 2025
    How to fix overcurrent during acceleration in Veichi DC Drives?
    • B
      Brandi NovakNov 22, 2025
      If you are experiencing overcurrent during acceleration with your Veichi DC Drives, the possible causes are: the inverter’s output circuit is grounded or shorted; the control mode is vector and no parameters identification was done; the acceleration time is too short; the voltage is too low; initiating a start on the motor while it is still running; a sudden load added while accelerating; the model of inverter is too small; the braking resistor is short. To resolve this, you can: eliminate the peripheral failure; initiate the identification of motor parameters; increase acceleration time; adjust the voltage to the normal range; choose rotational speed tracking start or start it after the motor stops; cancel the sudden load addition; use the inverter that has a higher power level; check if ...
  • T
    Teresa WatersSep 10, 2025
    What causes large speed deviation in Veichi DC Drives?
    • X
      xmezaSep 10, 2025
      Large speed deviation in Veichi DC Drives can be caused by: incorrectly set encoder parameters; the motor auto-tuning not being activated; or incorrect settings for F9-69 and F9-70. To resolve this: set the encoder parameters properly; perform the motor auto-tuning; or set F9.69 and F9.70 correctly based on the actual situation.
  • S
    Samantha RichardsonSep 12, 2025
    What to do in case of external equipment fault in Veichi DC Drives?
    • D
      Daniel OrozcoSep 12, 2025
      If you encounter an external equipment fault in Veichi DC Drives, where the external fault signal is input via Terminal X or virtual I/O, reset the operation.
  • S
    Sherry RochaSep 4, 2025
    What to do if Veichi DC Drives show input phase loss?
    • J
      Jared GreenSep 4, 2025
      If Veichi DC Drives show an input phase loss, it could be due to: abnormal three-phase input power; drive board malfunctions; lightening protection board malfunctions; or main control board malfunctions. Suggested actions are: check and eliminate problems in the peripheral circuit. For issues with the drive board, lightening protection board, or main control board, contact tech support.
  • S
    Steven ToddSep 2, 2025
    What causes power supply failure in Veichi DC Drives?
    • A
      Ashley MoralesSep 2, 2025
      Power supply failure in Veichi DC Drives is caused by the input voltage not being within the range of regulation. To fix this, adjust the input voltage to the range of regulation.

Veichi JT550 Series Specifications

General IconGeneral
Input Voltage3-phase 380V AC ±15%
Output Voltage0~Rated Input Voltage
Control ModeV/F control, sensorless vector control, closed-loop vector control
ProtectionOvercurrent, overvoltage, overheat, short circuit, phase loss
CommunicationRS485, Modbus
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to 60°C
Altitude≤1000m (above 1000m, derating required)
Frequency Range0-400Hz
Overload Capacity150% for 60 seconds
HumidityLess than 95%RH, no condensation