Connecting a Door
Installation
Ensure power is disconnected from the AC62 and locking hardware before wiring, removing or inserting
cassettes, readers, locks or any other peripherals.
Warning
The AC62 comes equipped with a Form C relay that can be driven dry or wet. AC41 is rated to power 12V locks
up to 1A and 24V locks up to 500mA.
1. Wiring Fail Secure and Fail Safe Locking
Hardware
Fail secure and fail safe are ways of conguring
locking hardware:
• Fail secure hardware locks when power is
interrupted. Usually uses NO (Normally Open
Conguration)
• Fail safe hardware unlocks when power is
interrupted. Usually uses NC (Normally Closed
conguration)
None/Dry
The AC62 does not provide power to the locking hardware (typically used with external power supplies).
Wet
The AC62 provides 12V or 24V power to the locking hardware.