NetSure 731 A41 插框电源系统
用户手册
NetSure 731 A41 Subrack Power
System
User Manual
资料版本 V1.1
归档日期 2017-12-31
BOM 编码 31013139
Version V1.1
Revision date December 31, 2017
BOM 31013139
维谛技术有限公司为客户提供全方位的技术支
持,用户可与就近的维谛技术有限公司办事处
或客户服务中心联系,也可直接与公司总部联
系。
维谛技术有限公
版权所有,保留一切权利。内容如有改动,恕
不另行通知。
维谛技术有限公
地址:深圳市南山区学苑大道 1001 号南山智园
B2
邮编:518055
公司网址:www.vertivco.com
客户服务热线:4008876510
E-mailvertivc.service@vertivco.com
Vertiv Tech provides customers with technical
support. Users may contact the nearest Vertiv
local sales office or service center.
Copyright © 2017 by Vertiv Tech Co., Ltd.
All rights reserved. The contents in this document
are subject to change without notice.
Vertiv Tech Co., Ltd.
Address: Block B2, Nanshan I Park, No.1001
Xueyuan Road, Nanshan District, Shenzhen,
518055, P.R.China
Homepage: www.vertivco.com
E-mail: overseas.support@vertivco.com

Questions and Answers

  • J
    John SchultzAug 18, 2025
    What to do if the Vertiv Tech NetSure 731 A41-S1 Power Supply DC voltage is low?
    • J
      Jeffery SmithAug 18, 2025
      If the DC voltage is low, first check if it's due to a mains failure; if so, disconnect some loads to extend system operation. Next, verify the DC under-voltage value set in the controller and correct it if needed. Also, check for inoperative rectifiers or ones with no output current, and replace them if found. Finally, ensure the total rectifier current exceeds the total load current during float charge; if not, reduce loads or add rectifiers so the rectifier current is at least 120% of the load current with one redundant rectifier.
  • R
    robertjonesAug 21, 2025
    How to fix AC voltage high on Vertiv Tech NetSure 731 A41-S1?
    • R
      rowechristineAug 21, 2025
      If the AC voltage is too high, check if the AC over-voltage value is set too low and adjust it accordingly. Note that a slight over-voltage might not impact the system. However, the rectifiers will cease operation if the mains voltage exceeds 305V. If the mains voltage consistently surpasses the AC over-voltage value, improvements to the mains grid are necessary.
  • K
    kathy66Aug 23, 2025
    Why is the AC voltage low on my Vertiv Tech NetSure 731 A41-S1 Power Supply?
    • C
      christine14Aug 23, 2025
      If the AC voltage is low, check if the AC under-voltage point is set too high and adjust it if necessary. Be aware that when the mains voltage drops below 176V, the rectifier output power will be derated, and below 80V, the rectifiers will stop working. If the mains voltage is consistently below the AC under-voltage value, the mains grid needs improvement.
  • J
    Justin JohnsonAug 26, 2025
    How to troubleshoot high DC voltage on Vertiv Tech Power Supply?
    • J
      James WebbAug 26, 2025
      If the DC voltage is high, check the DC over-voltage value via the controller and correct it if it's set inappropriately. If the setting is correct, identify the faulty rectifier by: 1. Ensuring the batteries operate normally. 2. Switching off AC input to all rectifiers. 3. Powering on rectifiers one at a time. If over-voltage protection triggers when a specific rectifier is powered on, replace that faulty rectifier.
  • M
    Mr. Edward ArmstrongAug 28, 2025
    How to fix a rectifier failure on Vertiv Tech Power Supply?
    • M
      Mark SmithAug 28, 2025
      If a rectifier has a red fault indicator, it is faulty. Power off the rectifier, wait a moment, and then power it back on. If the alarm continues, replace the rectifier.
  • T
    Thomas WatsonAug 30, 2025
    What to do if the Vertiv Tech NetSure 731 A41-S1 rectifier fan fails?
    • M
      mfosterAug 30, 2025
      If a rectifier fan fails, first check if the fan is obstructed. If it is, clean the obstruction and push the rectifier back into place. If the fan is not obstructed, or the problem continues after cleaning, replace the rectifier.
  • F
    Felicia WrightSep 1, 2025
    What to do when Vertiv Tech NetSure 731 A41-S1 Power Supply reports a mains failure?
    • K
      Kayla HayesSep 1, 2025
      If the cause of the mains failure is unknown or the failure lasts too long, a diesel generator is needed. Before using the generator power to supply the subrack power system, it is suggested to run the generator at least five minutes to minimize the impact on the subrack power system.
  • B
    Bridget GarciaSep 4, 2025
    What causes a Vertiv Tech NetSure 731 A41-S1 Power Supply rectifier to not respond?
    • M
      Martin SmithSep 4, 2025
      If a rectifier is not responding, check if the communication cable is properly connected between the rectifier and the controller. If it is, restart the rectifier. If the alarm continues, replace the rectifier.
  • T
    Tamara WilliamsSep 6, 2025
    Why is my Vertiv Tech NetSure 731 A41-S1 rectifier in protect mode?
    • J
      Juan GarciaSep 6, 2025
      If the rectifier is in protect mode, check if the mains voltage is above 305V or below 80V. If the mains voltage is under the AC under-voltage value or above the AC over-voltage value, the mains grid should be improved.
  • A
    Anna LewisSep 8, 2025
    What should I do if my Vertiv Tech NetSure 731 A41-S1 reports a high temperature?
    • K
      Kimberly WolfSep 8, 2025
      If a high temperature is reported, check if the temperature of the temperature sensor is too high. If it is, find the causes and cool down the battery compartment.

Summary

Safety Precautions

Electrical Safety and Hazards

Covers electrical dangers, tools, thunderstorm, ESD, short circuits, and dangerous energy.

Chapter 1 Overview

Chapter 2 Installation Instruction

Safety Regulations and Preparation

Outlines safety rules, unpacking inspection, and cable selection guidelines.

Electrical Installation and Cabling

Details methods for cabling, connecting AC, load, battery, and signal cables.

Chapter 3 Commissioning

Chapter 4 Troubleshooting

Controller Alarms and Fault Handling

Details controller alarm types, fault handling, and replacement procedures.

Appendix 2 Installation Instruction of Battery Rack

Vertiv Tech NetSure 731 A41-S1 Specifications

General IconGeneral
ModelNetSure 731 A41-S1
Product TypeDC Power System
Input Voltage85-300V AC
Output Voltage-48V DC
Height2000 mm
Dimensions600 x 600 x 2000 mm
MountingRack Mount
Operating Temperature-40°C to 45°C
Efficiency>96% (Rectifier)