EasyManua.ls Logo

Vertiv Liebert MCS028 - Page 101

Vertiv Liebert MCS028
127 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Models
Figure # in Figure 10.1
above
Importance Factor Iρ= 1.0 Importance Factor Iρ= 1.5
Maximum Compressive
Reaction lb
Maximum Anchor
Maximum Compressive
Reaction lb
Maximum Anchor
Tensile
lb
Shear
lb
Tensile
lb
Shear
lb
Without
Receiver
Figure 1 37 14 14 47 24 21
With
Receiver
Figure 2 43 15 23 56 27 35
MCL055
Without
Receiver
Figure 1 37 14 14 47 24 21
With
Receiver
Figure 2 43 15 23 56 27 35
* All loads are calculated per ASCE 7-05, Chapter 13.6 Sds = 2.0, Rρ = 6.0, a = 2.5
Source: DPN002414 Rev. 3
Table 10.1 Seismic anchorage loads for one-fan models (continued)
Vertiv | Liebert® MC Installer/User Guide | 101

Table of Contents

Other manuals for Vertiv Liebert MCS028

Related product manuals