39
1. Press OK + å simultaneously and hold for
approx. 4 s.
2. "Factory settings"
3. Confirm "Yes" with OK.
The following settings are reset:
■
"Time program"
■
"Holiday program" is ended.
■
The "Background vent." operating program is set.
■
"Intensive mode" or "Economy mode" are
switched off.
■
"Date" is set to 01.09.2016.
■
"Language" is set to "German".
■
"Contrast" and "Brightness" default back to the
factory settings.
■
Parameter settings:
All unmarked and marked parameters
!
default
back to the factory settings: See page 20.
■
The "Message list" is deleted.
Vitovent 200-C Function check
1. Press OK + å simultaneously and hold for
approx. 4 s.
2. "Function check"
3. Use / to select the function.
4. Confirm with OK.
■
The selected function is enabled.
■
"Ventilation: Overview" appears on the display.
5. Use to terminate the selected function.
The following functions can be tested:
Function System characteristics
"Fan" The fans are switched on.
The following steps are repeated cyclically:
1. The fans are controlled with 10 V for 120 s.
2. The fans are controlled with 1.7 V for 120 s.
3. The fans are controlled with 0 V for 10 s.
"Preheating coil ON"
■
The fans are controlled with 1.7 V.
■
The electric preheating coil is switched on and regulated to the cur-
rent actual outdoor air temperature plus 10 K.
"Bypass" The fans are controlled with 1.7 V. Any open bypass will be closed.
The following steps are then repeated cyclically:
1. The bypass is opened.
2. The bypass remains open for 60 s.
3. The bypass is closed.
4. The bypass remains closed for 60 s.
Service functions
Factory settings
5816558