58
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
Standard ventilation C10B
■
Type H32S C325:
150 m
3
/h
■
Type H32S C400:
200 m
3
/h
Intensive ventilation C10C
■
Type H32S C325:
250 m
3
/h
■
Type H32S C400:
300 m
3
/h
Bypass operation C1A0 0
Central heating and heat recovery C1A1 0 Do not adjust!
Set temperature for reheating coil C1A4 210 (≙ 21 °C) Do not adjust!
CO2 sensor 1 min PPM C1C8 400 ppm
CO2 sensor 1 max PPM C1C9 1200 ppm
CO2 sensor 2 min PPM C1CA 400 ppm
CO2 sensor 2 max PPM C1CB 1200 ppm
CO2 sensor 3 min PPM C1CC 400 ppm
CO2 sensor 3 max PPM C1CD 1200 ppm
CO2 sensor 4 min PPM C1CE 400 ppm
CO2 sensor 4 max PPM C1CF 1200 ppm
Set temperature for reheating coil C1A4 210 (≙ 21 °C)
Sensitivity, humidity sensor C1A6 0
Automatic changeover summertime - winter-
time
7781 1
Duration, economy mode 7D84 72 h
Duration, intensive mode 7D85 12 ≙ 120 min
Start summertime - month 8682 3
Start summertime - week 8683 5
Start summertime - day 8684 7
Start wintertime - month 8685 10
Start wintertime - week 8686 5
Start wintertime - day 8687 7
Commissioning/service reports
Parameters (cont.)
5816558
Appendix