57
Vitovent 300-C
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
Enable Vitovent 7D00 0
Preheating coil C101 1
Reheater coil C102 0 Do not adjust!
Humidity sensor C105 0
Set CO2 level C106 0 Do not adjust!
Set extract air temperature C108 220 (≙ 22 °C)
Background vent. C109
30 m
3
/h
Reduced ventilation C10A
75 m
3
/h
Standard ventilation C10B
100 m
3
/h
Intensive ventilation C10C
125 m
3
/h
Bypass operation C1A0 0
Central heating and heat recovery C1A1 0 Do not adjust!
Imbalance permitted C1A2 1
Specified imbalance C1A3 0
Set temperature for reheating coil C1A4 210 (≙ 21 °C) Do not adjust!
Sensitivity, humidity sensor C1A6 0
Min. temperature, geoth. heat exchanger C1AA 50 (≙ 5 °C)
Max. temperature, geoth. heat exchanger C1AB 250 (≙ 25 °C)
Function, input 1 C1B0 0
Min. voltage, input 1 C1B1 0 (10 ≙ 1 V)
Min. voltage, input 2 C1C1 0 (10 ≙ 1 V)
Flow rate correction C1C7 100
Automatic changeover summertime - winter-
time
7781 1
Continuous operatn ON/OFF 7D83 2
Duration, economy mode 7D84 72 h
Duration, intensive mode 7D85 12 ≙ 120 min
Start summertime - month 8682 3
Start summertime - week 8683 5
Start summertime - day 8684 7
Start wintertime - month 8685 10
Start wintertime - week 8686 5
Start wintertime - day 8687 7
Vitovent 300-W
Parameter Code Delivered condition Commission-
ing
Maintenance/
service
Enable Vitovent 7D00 0
Preheating coil C101 1
Humidity sensor C105 0
Set CO2 level C106 0
Set extract air temperature C108 200 (≙ 20 °C)
Background vent. C109
50 m
3
/h
Reduced ventilation C10A
100 m
3
/h
Commissioning/service reports
Parameters (cont.)
5816558
Appendix