36
Indoor unit: Main PCB (230 V~ components)
Information regarding the connection values
The specified output is the recommended connected
load.
Total output of all components connected directly to
the heat pump control unit (e.g. pumps, valves, mes-
sage facilities, contactors): Max. 1000 W
If the total output is < 1000 W, the individual rating of
a component (e.g. pump, valve, message facility,
contactor) can be greater than specified. However,
the breaking capacity of the relevant relay must not
be exceeded.
The specified current indicates the max. switching
current of the switching contact. Observe total cur-
rent of 5 A.
Set the required parameters during commissioning:
See page 68 onwards.
Plug
sYA
Terminals Function Explanation
211.2
1.
Secondary pump
In systems without a heating water buffer cylinder, no
other heating circuit pump is required:
See terminal 212.2.
Connect a temperature limiter to restrict the maximum
temperature for underfloor heating circuits (if instal-
led) in series.
Connection values
Output: 140 W
Voltage: 230 V~
Max. switching current: 4(2) A
211.5
AC
Type AWOT(-M)-E-AC:
3-way diverter valves for heating wa-
ter buffer cylinder bypass in cooling
mode
Connect the 3-way diverter valves in parallel.
Connection values
Output: 10 W
Voltage: 230 V~
Max. switching current: 4(2) A
Plug
sYS
Terminals Function Explanation
212.2
A1
Heating circuit pump for heating cir-
cuit without mixer A1/HC1
This pump is connected in addition to the secondary
pump if a heating water buffer cylinder is installed.
Connect the temperature limiter to restrict the maxi-
mum temperature for underfloor heating systems (if
installed) in series.
Connection values
Output: 100 W
Voltage: 230 V~
Max. switching current: 4(2) A
212.3 DHW circulation pump Connection values
Output: 50 W
Voltage: 230 V~
Max. switching current: 4(2) A
212.4 3-way diverter valve for heating water
buffer cylinder bypass or heat pump
in the case of dual alternative mode
Connection values
Output: 130 W
Voltage: 230 V~
Max. switching current: 4(2) A
Installation sequence
Electrical connection (cont.)
5831412