20
Menu selection Vitotronic control unit
V050HK1W Vitotronic 050, type HK1W, HK1S
Vitotronic 200-H, type HK1W, HK1S
V050HK1M Vitotronic 050, type HK1M
Vitotronic 200-H, type HK1M
V050HK3 Vitotronic 050, type HK3W, HK3S
Vitotronic 200-H, type HK3W, HK3S
V100GC1 Vitotronic 100, type GC1
V200GW1 Vitotronic 200, type GW1
V300GW2 Vitotronic 300, type GW2
V333MW1S Vitotronic 333, type MW1, MW1S
Vitotronic 300-K, type MW1, MW1S
V333MW2 Vitotronic 333, type MW2
Vitotronic 300-K, type MW2
VScotHC Vitotronic 100, type HC1, HC2
VScotHO1 Vitotronic 200, type HO1
VPlusHC Vitotronic 100, type HC1, HC2
VPlusHO1 Vitotronic 200, type HO1
Vitotronic 200, type KW6
VDensHC Vitotronic 100, type HC1, HC2
VPendHC Vitotronic 100, type HC1, HC2
VDensHO1 Vitotronic 200, type HO1
VPendHO1 Vitotronic 200, type HO1
2. Anlagen Nummer
Menu for the selection of the Viessmann
system number to be assigned to the
corresponding communication object.
Menu selection: 1 to 5
If several systems are connected to a
LON, a number is assigned to each sys-
tem.
Up to 5 systems are possible. A system
may comprise up to 4 boilers, up to 32
heating circuit control units and 1 cas-
cade control unit.
Note
The Viessmann system number must
also be programmed into the Vitotronic
control unit selected under "Regelung"
(for coding, see page 13).
3. Teilnehmer-Nummer
Menu for the selection of the subscriber
number to be assigned to the corre-
sponding communication object.
Menu selection: 1 to 97
If several Vitotronic control units are inte-
grated into the LON, a number will be
assigned to each one of them.
A total of 97 Vitotronic control units can
be integrated into a single LON.
Commissioning
Parameters in ETS
(cont.)