13
Appendix
Specification
Rated output kW 40 50 63 80 100
Product ID
ćĂacc. to the Efficiency Directive
ćĂacc. to the Gas Device Directive
CEĆ0645 AUĂ114
CEĆ0197 AUĂă21
Flue gas resistance
hPa
mbar
0.08
0.08
0.10
0.10
0.13
0.13
0.25
0.25
0.45
0.45
Required draught
*1
Pa
mbar
5
0.05
5
0.05
5
0.05
5
0.05
5
0.05
Flue gas characteristics
Temperature
*2
at
ćĂboiler water temp. 40ĂºC
ćĂboiler water temp. 75ĂºC
ºC
ºC
155
180
155
180
155
180
155
180
145
170
Product characteristics (to EnEV)
EfficiencyĂη at
ć 100
Ă% rated output
ćă30
Ă% rated output
%
%
92.8
94.7
93.2
94.3
93.1
94.9
92.3
94.0
93.0
94.2
Standby lossesĂq
B,70
% 0.7 0.6 0.5 0.5 0.4
Power consumption
*3
at
ć 100
Ă% rated output
ćă30
Ă% rated output
W
W
264
88
294
98
329
110
369
123
410
137
*1
Observe when sizing the chimney stack.
*2
Flue gas temperatures as actual gross values to ENĂ304 (measurement with
5Ăthermocouples) at 20ĂºC combustion air temperature.
*3
Standard characteristics (in conjunction with VitoflameĂ200 oil pressure jet burner).
5692Ă531ĂGB