Ensure electrical and oil supply lines are disconnected before commencing work.
Set the burner into the servicing position as per the boiler service manual.
Clean strainer, filter, fuel lines, and tank, and remove any water present.
For 40kW or 50kW appliances, detach the burner flame tube.
Loosen the three nuts securing the burner to the boiler door and carefully withdraw the burner.
Remove the 3 socket head bolts securing the mixing assembly cover and slide it off.
Remove the existing nozzle and install the kerosene nozzle from the conversion kit.
Disconnect the oil pre-heater plug and connect the supplied link wire between brown and black wires.
Fasten a cable tie around the electrical supply cable, 3mm from the outer insulation end.
Pull the pre-heater cable until the tie is against the grommet, then secure with a second tie on the opposite side.
Reassemble and reinstall the burner into the appliance following the reverse order of disassembly.
Verify the electrode position and ensure the correct electrode spark gap is set.
Recommission the burner using new pump pressures, chamber pressure, and air settings from the table.