EasyManua.ls Logo

Vimar VIGAS series - Page 10

Vimar VIGAS series
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Gasifying boilers VIGAS
ENTER“
By buttons set the parameter you want to edit and by
pressing „ENTER“ button, the value starts to flash. buttons
set requested value.
end
Choose shotdown temperature of the boiler
Increase or decrease the value, maximal output will be
changed. Is adviced to decrease the value in transition
period (boiler tar level will drop).
Â
Brightness
Roll
Press „yes“ will acitivate the value rolling (Pic.6/2)
Help 0s
Set the time when graphical control will be indicated
4.1.5 Disconnection the boiler (Automatically)
4.2 TEMPERATURE SETTINGS OF OUTLET WATER
4.3 PARAMETERS SETTING OF VIGAS BOILER
When temperature drops under the shotdown temperature (see
Parameter settings of Vigas boiler in basic configuration) boiler is
switch-off automatically. „END“ will be indicated on the display. By
pressing „ENTER“ boiler will start operating again.
To call temperature setting hold „ENTER“ button at any boile
r
status. Symbol of the temperature setting will be indicated on the
display. Press „ENTER“ again. Symbol of the nominal output will
be indicated on the display with value, together with temperature o
f
outlet water in °C. By pressing the „ENTER“ button, the value start
to flash.
ENTER
Temperature is flashing, by using
buttons
choose requested
value. Button will exit the
temperature settings.
To call parameters setting hold „ENTER“ button at any boile
r
status and by pressing button. Press „ENTER“ again Symbol o
f
the parameters setting will be indicated on the display. By pressing
the „ENTER“ button twice, the values you can set will be indicated
on the display.
„ENTER“ENTER“