Maximum one-way distance
(feet) for 2% Voltage loss
(30A)
Maximum one-way distance
(feet) for 2% Voltage loss
(40A)
Maximum one-way distance
(feet) for 2% Voltage loss
(60A)
Table: Selection of cable size and length versus current
L. Fault Indications
PROTECTIONS & FAULT INDICATIONS WITH CAUSES
CHARGER OUTPU: OFF= No Output
REMOTE CONTROL UNIT &
LCD Fault Display
Output power decreases due to
high operating ambient
temperature
ON At reduced power in 25% step leading
to output off high temperature protection
see next row
no specific indication for high
temperature decreased output
Auto return to full set
power gradually as
unit temp cools down
charger over heat, OTP
protection on
OFF Manual power on off reset after fault
cleared
Alarm flash & Buzzer on “Charger
High Temp”
Charger preset to reduced output
power
ON At reduced output power as selected
Indicates “xx% Power Set”
This is not a fault!!
So no specific
indication
Battery over heat detected by
remote temp sensor at (60°C)
OFF Manual power on off reset after fault
cleared
Alarm flash & Buzzer on “Bat Over
Temp”
OFF Manual power on off reset after fault
cleared
Alarm flash & Buzzer on “Fan Fault”
Output Over Voltage Protection
when output voltage is 4%
higher than it should be for the
battery type and charge stage
OFF Manual power on off reset after fault
cleared
Alarm flash & Buzzer on “Output V
High”
To protect battery and
load connected.
Overload/ Over Current
Protection when output current
is 10% higher than the rated
maximum level
OFF Manual power on off reset after fault
cleared
Alarm flash & Buzzer on “Overload”
Short Circuit for > 20 sec
OFF Manual power on off reset after fault
cleared
Alarm flash & Buzzer on “Output
Shorted”
Short Circuit for < 20 sec
ON Charger returns to normal after fault
cleared
Reverse Polarity Protection
(Thermal Fuse)
OFF Manual Power on off reset after
correct fuse replaced
Alarm flash & Buzzer on
“WRONG POLARITY”