Installation Instructions – Electrical
CX33A/35A &CX98/99 Device
GENERAL INFORMATION
ELECTRICAL SPECIFICATIONS
Voltage...............................................................24 VDC
Current...............................................................0.4 A
Current on arming...........................................300-mS 16-A in-rush
External alarm dry contacts (NO and C)....24 VDC, 1 A rating
Normally closed inputs ..................................Fire alarm (FA; required)
External inhibit (EI)
Door position switch (DPS)
The Von Duprin Chexit device is designed for accident hazard or fire exit applications. It meets both life
safety and security needs as well as all requirements of NFPA101 for “Special Locking Arrangement” and
UBC “Special Egress-Control Devices.”
The Von Duprin Chexit device sounds an alarm and keeps an exit door secured for 15 seconds following an
attempt to exit. The Chexit releases immediately upon a fire alarm condition.
®
PUSH UNTIL ALARM SOUNDS
DOOR CAN BE OPENED
IN 15 SECONDS
CX Rim Exit Device
(CX98/99 shown)
Chexit Module
Cable
Door Sign
T
M
T
HE
®
Do not exceed rated
specifications.
WARNING
!
The Chexit device must be
installed in accordance
with these instructions by
a qualified electrician.
WARNING
!
Wiring must be in
accordance with all local
codes and regulations.
WARNING
!
VON DUPRIN
®
911352-00
Question and Answer IconNeed help?

Do you have a question about the Von Duprin Chexit CX33A/35A and is the answer not in the manual?

Von Duprin Chexit CX33A/35A Specifications

General IconGeneral
BrandVon Duprin
ModelChexit CX33A/35A
CategoryDoor Opening System
LanguageEnglish

Summary

General Information and Electrical Specifications

Electrical Specifications

Details voltage, current, and contact ratings for the Chexit device.

Pre-Installation Checklist

Mechanical Preparation

Steps for preparing the door and frame for device installation.

Electrical Preparation

Steps for wiring and component placement before installation.

Typical Wiring

Single Door Application Wiring

Diagrams and component list for wiring a single door Chexit.

Double Door Application Wiring

Wiring details for ganged Chexit devices on double doors.

Installation Steps

Prepare Device for Wiring

Remove end cap, bracket, and cover plate before wiring.

Drill Cable Hole and Route Wire

Drill a 5/8" hole and route the Chexit cable through the door.

Connect Power Transfer Wires

Connect device wires to power transfer door side wires.

Install Module into Cover Plate

Slide the Chexit module into the cover plate as shown.

Install Key Cylinder

Install the key cylinder if available, or proceed to step 6.

Route Cables and Make Connections

Route cables, connect pushpad, solenoid, and Chexit cables.

Position Connectors and Slide Module

Position connectors and slide module into mechanism case.

Install End Cap and Bracket

Install the end cap bracket and end cap, ensuring cable fits.

Install Door Sign

Remove backing from sign and place it on the door above the Chexit.

Proceed to Operation Testing

Advance to the 'Operation' section for testing and troubleshooting.

Operation and Troubleshooting

Chexit Mode Summary

Details actions, modes, LED indicators, alarm status, and duration.

Troubleshooting Guide

Identifies common symptoms, problems, and their solutions.

Chexit Options and Settings

Rearm Time Configuration Notes

Important notes for setting and configuring rearm times.