Pump not running.
"Pump" LED does
not light up*.
Power supply is interrupted. Ensure correct power supply.
Time switch function does not start the
pump. (BWO 155 Z)
Check "Operating state" LED.
Wait for next pump start.
Change time setting.
Timer, p. 11
Temperature function does not start the
pump (BWO 155 ERT).
Change shutdown temperature or wait for
next pump start.
Electronic regulating
thermostat ERT, p. 12
"Time" LED
ashes*.
Power supply was interrupted. Update time. Timer, p. 11
Pump is not
running: LED
"Pumpe" (pump)
is illuminated.*
Motor is defective (electrical/electronics). Replace motor.
Rotor is blocked because the rotor bearing is
defective.
Rotor is blocked by debris. Clean wetted parts. Maintenance, p. 15
Pump stops the
rotor continu-
ously.
Air in the pump housing, dry run protection
is active.
Bleed the circulation line. Installation, p. 6 and
Venting, p. 9
Pump makes
noise.
Air in the pump housing. Bleed the circulation line. Installation, p. 6 and
Venting, p. 9
Rotor bearing defective. Replace the rotor. If the bearing pin is
damaged exchange the motor.
Replacement, p. 17
Non-return valve is loose. Exchange the V-type pump housing or non-
return valve installed behind the pump
(e.g. RV 153).
Installation, p. 5
Faults and remedies
Observe the chapter “Safety” (see p. 3).
*only Pumps BWO 155 Z and/or BWO 155 ERT
Fault Cause Remedy Chapter/page