EasyManua.ls Logo

Watlow 942 Series - Chapter 2; Output 1 Wiring

Watlow 942 Series
63 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Install and Wire, Chapter 2
14
WATLOW Series 942 User's Manual
Output 1 Wiring
Figure 18 -
Process, 0 - 5VDC,
Output 1 Wiring.
Figure 19 -
Solid State Relay
Without Contact
Suppression, Output
1 Wiring.
Process, 0 - 5VDC, Output 1
Model # 942A - _ H _ _ - _ 000
Process Output
Proportional value determined by the control to balance the sensor input and set point. This
value will fall between 0 - 5VDC depending on the thermal characteristics of the system.
Load impedance is 10KΩ minimum.
18
17
Process, 0-5VDC, Non-Isolated
External
Load
-
++
-
Solid State Relay Without Contact Suppression
Watlow's solid state relay changes state at zero volts, which is "zero-cross switching." They
are also optically isolated, which means the output circuitry is energized by infrared light
striking a photosensitive device. This results in a virtual absence of electrically generated
noise, plus output to input electrical isolation. Off state impedance is nearly infinite and
should be used to switch high impedance non-inductive loads.
N.O.
COM.
External
Load
Fuse
L1
L2
18
17
Solid State Relay, Form A, 0.5 Amp
Solid State Relay Without Contact Suppression, Output 1
Model # 942A - _ K _ _ - _ 000