DT-200
version 3
Dual Technology • Low Voltage
Occupancy Sensor
with Light Level, Isolated Relay and Manual On features
SPECIFICATIONS
Voltage ............................................................................. 18-28VDC/VAC
Current Consumption ..................................................................... 25mA
Power Supply .................................................WattStopper Power Packs
Isolated Relay Rating ..................................................... 1A @30VDC/VAC
Operating Temperature ................................... 32° to 131°F (0° to 55°C)
Light Level One-Step Adjustment ...................................10FC to 200FC)
Time Delay Adjustment ...................................30 seconds to 30 minutes
Walk-Through Mode ..................3 minutes if no activity after 30 sec.
Test Mode ...................................................5 sec. or DIP switch reset
PIR Coverage (Typical) ................................................................ 1000 ft2
Sensitivity Adjustment .................... High or Low (DIP switch setting)
Ultrasonic Coverage (Typical) .............................................. 800-1200 ft2
Sensitivity Adjustment .................... Minimum to Maximum (trimpot)
Frequency ................................................................................. 40kHz
Installation Instructions
Santa Clara, CA 95050

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watt Stopper DT-200 and is the answer not in the manual?

Watt Stopper DT-200 Specifications

General IconGeneral
BrandWatt Stopper
ModelDT-200
CategoryAccessories
LanguageEnglish

Related product manuals