EasyManua.ls Logo

Watts Aerco INN 1060N - Page 34

Watts Aerco INN 1060N
39 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Innovation Water Heaters Edge [i] Controller
Venting and Combustion Air Design Guide
TAG-0090_A GF-5056 2/20/2020 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 34 of 39
TABLE 7: Innovation 1060N MBTU Water Heater Heater Continued
Inlet Duct
& No.
Units
Duct
Section
Type
Outside Air Temperature
-30 °F
-15 °F
0 °F
20 °F
40 °F
60 °F
80 °F
100 °F
120 °F
-34 °C
-26 °C
-18 °C
-7 °C
4 °C
16 °C
27 °C
38 °C
49 °C
10" Duct
Three
Units
Straight Run
0.28
0.30
0.31
0.33
0.35
0.38
0.40
0.43
0.46
90° Elbow
2.07
2.17
2.27
2.43
2.59
2.76
2.95
3.14
3.35
(631)
(661)
(692)
(741)
(789)
(841)
(899)
(957)
(1021)
45° Elbow
1.58
1.66
1.74
1.86
1.98
2.11
2.26
2.41
2.57
(482)
(506)
(530)
(567)
(604)
(643)
(689)
(735)
(783)
Ent. Loss
4.59
4.82
5.06
5.4
5.76
6.14
6.55
6.99
7.46
(1399)
(1469)
(1542)
(1646)
(1756)
(1871)
(1996)
(2131)
(2274)
12" Duct
Three
Units
Straight Run
0.11
0.12
0.13
0.13
0.14
0.15
0.16
0.17
0.19
90° Elbow
0.65
0.68
0.71
0.76
0.81
0.86
0.92
0.98
1.05
(198)
(207)
(216)
(232)
(247)
(262)
(280)
(299)
(320)
45° Elbow
0.49
0.51
0.54
0.57
0.61
0.65
0.69
0.74
0.79
(149)
(155)
(165)
(174)
(186)
(198)
(210)
(226)
(241)
Ent. Loss
1.25
1.31
1.37
1.46
1.56
1.67
1.78
1.9
2.02
(381)
(399)
(418)
(445)
(475)
(509)
(543)
(579)
(616)
12" Duct
Four Units
Straight Run
0.4
0.42
0.45
0.47
0.51
0.54
0.58
0.61
0.65
90° Elbow
2.58
2.71
2.84
3.03
3.24
3.45
3.68
3.93
4.19
(786)
(826)
(866)
(924)
(988)
(1052)
(1122)
(1198)
(1277)
45° Elbow
1.95
2.04
2.14
2.29
2.44
2.6
2.78
2.96
3.16
(594)
(622)
(652)
(698)
(744)
(792)
(847)
(902)
(963)
Ent. Loss
4.99
5.23
5.49
5.86
6.25
6.66
7.11
7.59
8.09
(1521)
(1594)
(1673)
(1786)
(1905)
(2030)
(2167)
(2313)
(2466)
14" Duct
Four Units
Straight Run
0.13
0.14
0.15
0.16
0.17
0.18
0.19
0.2
0.22
90° Elbow
0.92
0.96
1.01
1.08
1.15
1.23
1.31
1.4
1.49
(280)
(293)
(308)
(329)
(351)
(375)
(399)
(427)
(454)
45° Elbow
0.70
0.74
0.77
0.83
0.88
0.94
1.00
1.07
1.14
(213)
(226)
(235)
(253)
(268)
(287)
(305)
(326)
(347)
Ent. Loss
2.04
2.14
2.25
2.4
2.56
2.73
2.91
3.11
3.32
(622)
(652)
(686)
(732)
(780)
(832)
(887)
(948)
(1012)
NOTES: 1) Calculation assumes 220 scfm (6.23 m
3
/min) per heater at full fire rate
2) Units for "Straight Run" pressure drop values are equivalent feet per foot (eq.
m/m)
3) Units for "Elbows" and "Ent. Loss" are equivalent feet per item (eq. m/item)

Other manuals for Watts Aerco INN 1060N

Related product manuals