Installation, Maintenance, and Repair Manual
Series LF007 Model IOT
Double Check Valve Assemblies
2½" – 3"
NOTICE
For Australia and New Zealand, line strainers should be installed
between the upstream shutoff valve and the inlet of the backflow
preventer.
Watts
®
product specifications in U.S. customary units and metric
are approximate and are provided for reference only. For precise
measurements, contact Watts Technical Service. Watts reserves
the right to change or modify product design, construction, spec-
ifications, or materials without prior notice and without incurring
any obligation to make such changes and modifications on Watts
products previously or subsequently sold.
RP/IS-LF007-IOT
Testing
For field testing procedure, refer to the Watts installation sheets
IS-TK-DL, IS-TK-9A, IS-TK-99E, and IS-TK-99D at
www.watts.com.
For other repair kits and service parts, refer to the Backflow
Prevention Products Repair Kits & Service Parts price list
PL-RP-BPD at www.watts.com.
For technical assistance, contact your local Watts representative.
WARNING
!
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information
can result in death, serious personal injury, property
damage, or damage to the equipment.
Keep this Manual for future reference.
Local building or plumbing codes may require modifications
to the information provided. You are required to consult
the local building and plumbing codes prior to installation.
If the information provided here is not consistent with
local building or plumbing codes, the local codes should
be followed. This product must be installed by a licensed
contractor in accordance with local codes and ordinances.
WARNING
!
Need for Periodic Inspection/Maintenance: This product
must be tested periodically in compliance with local codes, but
at least once per year or more as service conditions warrant.
All products must be retested once maintenance has been
performed. Corrosive water conditions and/or unauthorized
adjustments or repair could render the product ineffective for
the service intended. Regular checking and cleaning of the
product’s internal and external components helps assure
maximum life and proper product function.
WARNING
!
Series LF007 is designed for installation at referenced cross-
connections to prevent the backflow of polluted water into the
potable water supply. Model IOT (available only with NRS gate
valves) includes factory-installed pressure sensors on three test
cocks (No. 2, No. 3, and No. 4).
LF007-NRS-IOT
NOTICE
Use of integrated pressure sensors on and monitoring connection
kit with IOT models does not remove the need to comply with all
required instructions, codes, and regulations related to installation,
operation, and maintenance of the backflow preventer.
Watts is not responsible for data transmission failures due to
power issues.
NOTICE
For IOT models, an add-on monitoring connection kit is required
to collect psi measurements from the integrated pressure sen-
sors. Without the connection kit, the pressure sensors are passive
components and will not communicate with any other device.
For BMS only. (The connection kit and pressure sensors are
also available for existing installations. See “Add-on Monitoring
Connection Kits,” for ordering details.)

Questions and Answers

  • M
    Marcus SanchezJul 29, 2025
    What to do if the Watts Control Unit check valve fails to hold 1.0 PSID minimum?
    • S
      Samantha ThomasJul 29, 2025
      If the check valve isn't holding the minimum pressure, here's what you can check: 1. Debris: Disassemble and clean the check disc sealing surface. 2. Leaking gate valve: Disassemble and clean or repair the gate valve. 3. Damaged components: Disassemble and replace the seat disc, seat O-ring, or the guide if it's damaged. 4. Spring: Disassemble and replace the spring if it's weak or broken.
  • M
    Michael RiveraAug 7, 2025
    What to do if low flows are passing through the mainline valve of my Watts Control Unit?
    • D
      Dr. Janice Gibson DVMAug 8, 2025
      If you're experiencing low flows, the following could be the cause: * Mainline check fouled: Disassemble and clean it. * Meter strainer plugged: Disassemble and clean the strainer. * Damaged components: Disassemble and replace the mainline seat disc or seat. * Broken spring: Disassemble and replace the mainline spring.
  • D
    David SchultzAug 19, 2025
    Why is my Watts Control Unit chattering during flow conditions?
    • T
      travisramosSep 12, 2025
      Chattering during flow conditions can occur if the guide is worn, damaged, or defective. Disassemble and repair or replace the guide.

Summary

Installation Guidelines

Indoors Installation

Series LF007 can be installed vertically or horizontally in an accessible location. Flush pipelines before installation.

Outside Building Installation

Install above ground where freezing conditions do not occur. Use insulated enclosure if freezing conditions are possible.

Parallel Installation

Consult local codes for parallel installation of multiple LF007 valves to serve larger pipes for continuous supply.

Servicing Check Valves

Check Valve Servicing Steps

Detailed steps for removing, cleaning, and reassembling check valve modules and components without special tools.

Troubleshooting Guide

Common Issues and Solutions

Addresses symptoms like failure to hold pressure, chatter, and low flow, providing causes and recommended solutions.

Add-on Monitoring Connection Kits

Monitoring Kit Options

Details on connection kits for transmitting pressure measurements from integrated sensors to a building management system.

Watts LF007 IOT Series Specifications

General IconGeneral
BrandWatts
ModelLF007 IOT Series
CategoryControl Unit
LanguageEnglish