avin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
W
avin Tempower Control Manual
Wavin Tempower Control
Heating and Cooling systems
.
19
66.. CCoommppoonneennttss ccoonnttrrooll
6
6
.
.
1
1
M
M
i
i
x
x
i
i
n
n
g
g
v
v
a
a
l
l
v
v
e
e
c
c
o
o
n
n
t
t
r
r
o
o
l
l
The WTC-3 can regulate mixing valves to set and keep
under control the inlet water temperature for heating and
cooling.
The built in program can keep the requested temperature
within +/- 0.3
°C.
The WTC-3 uses the PI regulation to keep an accurate
temperature. The PI regulation decreases over control and
stopped the wave effect within the shortest time.
Note
Any type of mixing valve controlled by 0-10V can be used.
The default inlet temperature values for heating:
45
°C
The default inlet temperature values for cooling:
16
°C
Both values can be modified in the software according to
request.
The Wavin temperature sensor must be placing after the
mixing valve and attached directly to the pipe!
Design Manual
Heating and Cooling systems
Design Manual
Heating and Cooling systems
Note
Use only Wavin temperature sensor.
Note
I
n case of overheating ( 60
°C
). the pump will stop to work
a
nd consequently this will cause a mixing valve failure.
Temperature sensor
WTC-3 can control the inlet cooling water temperature
according to relative humidity.