4
The models of LX3V-0806MX and LX3V-1208MX has RS485 communication port .
PIN Signal
Description
485A
485B
485+
485-
485+
485-
485A
485B
COM RS PIN2 48 5
LX3V-20MX
PWR
RUN
BAT
ERR
485A
485B
1 2 3
4
5
6
7
10
11 12
13
0
1 2
3
4
5
6
7
10 11 12
13
0
Part 8 Model
1:1S instruction
2:2N instruction
Default:2N instruction
R: relay
T: transistor
Basic unit
A:AC 2 2 0 V
D:DC 2 4 V
Output
Part 9 Electrical Specification
AC Power Supply
Model
LX3V/ LX3VP/ LX3VE/ LX3VM
26 points and below
LX3V/ LX3VP/ LX3VE/ LX3VM
above 26 points
Rated voltage
AC 100V ~ 240V
Voltage range
AC 85V ~ 264V
Rated frequency
50/60HZ
Power outage time
continue to work with less than 10ms power outage time
Power fuse
250V 1A
250V 3.15A
Impulse current
<20A 5ms/AC100V
Power (W)
20W
50W
Sensor power supply
DC 24V 700mA
DC Power Supply
Model
LX3V/ LX3VP/ LX3VE/ LX3VM
Rated voltage
DC 24V
Voltage range
DC 24V±10%
Power fuse
250V 3.15A
Impulse current
< 15A 1 ms/AC100V
Power (W)
<30W