EasyManua.ls Logo

Wecon LX3 Series - Page 7

Default Icon
10 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LX3 Series User Manual V2.0
7
DC
Lo a d
output s contact of '
programmable controller
inductive load
Fly wheel diode-
●If this is AC inductive load, make load and surge absorber in parallel, can reduce the noise.
output s contact of '
programmable controller
AC
Loa d
inductive load
surge absorber
The output contacts of the programmable control are best to use on the same phase side.
in-
phase
●Contactors of forward and reverse close very dangerous at the same time, like this load, except to
use internal program to do interlock control, on the outside of the programmable controller must also set
the interlock.
interlock
interlock
Forward limit
Reverse limit
Forward
Reverse
output s contact of '
programmable controller
Warning
Part 13 Terminal
Pin
LX3V/LX3VP/LX3VE/LX3VM series
L/N
AC 100V~240V
24V+/COM
Output +24V
Grounding
The empty post, never be connected
S/S
Support leakage input (connected to 24V+) or source
input (connected to COM).
X0-Xn
External input terminal
Y0-Yn, COMn
Output terminal, Group number