8 | W21 Magnet Drive System
®
Quick Guide
Procedure for oriented start-up (using nameplate data of motor 18.5kW as example)
1 Press “PRG”
2
- Select group “F0”.
- Press “Set”.
3
- Set “F0.00”
according to
motor control
algorithm “5: PM
Vector Control”.
- Press “Set”.
4
- Set “F0.11”
according to the
upper frequency.
- Press “Set”.
5
- Set “F0.08”
according to the
frequency aim.
- Press “Set”.
6
- Set “F0.09”
according to the
maximum frequency.
- Press “Set”.
7
- Select group
“F5”.
- Press “
Set”.
8
- Set “F5.01”
according to the
motor number of
poles.
- Press “Set”.
9
- Set “F5.02”
according to
the motor rated
power.
- Press “Set”.
10
- Set “F5.03”
according to
the motor rated
frequency.
- Press “Set”.
11
- Set “F5.04”
according to
the motor rated
speed.
- Press “Set”.
12
- Set “F5.05”
according to the
motor rated voltage.
- Press “Set”.
13
- Set “F5.06”
according to
the motor rated
current.
- Press “Set”.
14
- Set “F5.12” as “2:
Static Self-Tune“.
- Press “Set”.
To end press “Reset”.
To run the motor press “FWD”.
F
Note!
The configuration through the “Oriented Start-up” results in the automatic modification of the content of
parameters and internal variables of the inverter regarding the control and the motor. That ensures a stable
operation of the control and maximum efficiency of the motor.