Connecting the SAI Distributor
5663600000/1.4/09.09
77
5.11 SAI-AU M12 SB 4AO
The SAI distributor Active Universal is equipped with
the functions of a decentralised I/O system. Each
distributor is equipped with module-specific actua-
tor/sensor functions and a sub-bus interface. The
modules combine the complete electronics in a wa-
ter- and dust-proof protected housing. This enables
their use in harsh environments.
The module SAI-AU M12 SB 4AO is designed to
connect four analogue actuators with four M12 con-
nectors.
Figure 48 SAI-AU M12 SB 4AO
HINWEIS
After a change of the Subbus modules is
in many situations a new start of the ga-
teway necessary.
LEDs
UB Supply voltage UB
Supplies the module and the
Plug-in stations 1 to 4
Com Communication with the
gateway
AO0 to AO3 Analogue outputs
Connections
SUB IN Sub-bus input
SUB OUT Sub-bus output
1 to 4 4 inputs
Table 56 SAI-AU M12 SB 4AI
Connection of supply voltage
The power supply is 24 V DC in accordance with EN
61131-2; the permissible range is 18 to 30 V DC.
The distributor is designed to offer protection against
polarity reversal.
Module connection from SUB-IN
Contact system M8 male connector, 4-pole
Coding -
Pin assignment
Pin 1: + 24 Vdc
Pin 2: Data +
Pin 3: GND
Pin 4: Data -
Housing: Shield, connected
with the FE
Table 57 Contact assignment for the sub-bus
male connector
AO3
4AO
UB
COM
IN OUT
BUS
AO2
AO1
AO0