Weil-McLain 88 Water and steam boilers — Series 2 — for Gas, Light Oil, & Gas/Light Oil-Fired Burners
18 Part No. 550-100-068/1009
Connect steam boiler piping
(continued)
Drawing legend & notes
(Figure 23 through Figure 26)
Riser pipes (one for each supply intermediate section)
Horizontal pipes needed to offset the header to allow for expansion and contraction of the header
Steam supply must be located between last riser connection and equalizer elbow
Equalizer elbow — full size or reducing
Equalizer pipe
Close nipple at Hartford loop tee to reduce water hammer potential
Condensate return line (gravity or pumped)
Minimum 4 inches between water line and top of Hartford loop return nipple
Boiler water line — all automatic water level controls must be set to maintain this level
Minimum 24 inches between water line and bottom of header